Grid-Tied Remote Dispatch Examples
The following examples apply to grid-tied inverters, controlling grid connection point power via Modbus registers.
All examples use Function Code 10H (Write Multiple Registers), split into two control blocks.
Control Block 1 (Common)
Before sending Control Block 2, always send Block 1 to enable Remote Dispatch:
Command: 01 10 AC 44 00 05 0A 00 01 00 05 00 00 00 00 00 00 B1 5144100=1(ON)44101=5min failsafe44102–44104=0(no system limit)
Example: Zero Export
Set grid connection point power to 0, meaning all PV generation is consumed locally with no export to the grid.
Control Block 2 (registers 44105–44107):
Command: 01 10 AC 49 00 03 06 00 03 00 00 00 00 4D 2944105=3(Grid Import/Export Control)44106=0(zero export)
Example: Limit Export Power to 3 kW
When PV generation exceeds local load, limit the power exported to the grid to 3 kW.
Control Block 2 (registers 44105–44107):
Command: 01 10 AC 49 00 03 06 00 03 00 00 00 1E 4C A844105=3(Grid Import/Export Control)44106=30→ 3000 W export limit
Example: Import 2 kW from Grid
During peak consumption or at night, actively import 2 kW from the grid to supplement local demand.
Control Block 2 (registers 44105–44107):
Command: 01 10 AC 49 00 03 06 00 03 FF FF FF 38 4D 6A44105=3(Grid Import/Export Control)44106=-200→ 2000 W import (negative value = import)