Energy Storage Remote Dispatch Examples

The following examples apply to hybrid / energy storage inverters, controlling battery charge and discharge via Modbus registers.

All examples use Function Code 10H (Write Multiple Registers), split into two control blocks.

Control Block 1 (Common)

Before sending Control Block 2, always send Block 1 to enable Remote Dispatch:

Command: 01 10 AC 44 00 05 0A 00 01 00 05 00 00 00 00 00 00 B1 51
  • 44100 = 1 (ON)
  • 44101 = 5 min failsafe
  • 44102–44104 = 0 (no system limit)

Example 1: Battery Standby

Disable battery charge and discharge, maintaining the current SOC. PV generation is prioritized for local loads, with excess exported to the grid.

Control Block 2 (register 44105):

Command: 01 10 AC 49 00 01 02 00 01 05 C3
  • 44105 = 1 (Battery Standby)

Example 2: Battery Charging at 5 kW

Charge the battery at 5 kW from the grid or PV.

Control Block 2 (registers 44105–44107):

Command: 01 10 AC 49 00 03 06 00 02 00 00 01 F4 70 FE
  • 44105 = 2 (Charge/Discharge Control)
  • 44106 = 500 → 5000 W charge (positive value = charge)

Example 3: Battery Discharging at 3 kW

Discharge the battery at 3 kW to supply local loads or export to the grid.

Control Block 2 (registers 44105–44107):

Command: 01 10 AC 49 00 03 06 00 02 FF FF FF 24 4D 71
  • 44105 = 2 (Charge/Discharge Control)
  • 44106 = -300 → 3000 W discharge (negative value = discharge)